Go to Top
FAQs OIB guidelines 2015 - Österreichisches Institut für Bautechnik | OIB

Frequently asked questions

FAQs

Frequently asked questions

to the OIB guidelines 2015

The answers to the FAQs represent the interpretation of the relevant OIB guideline by the respective expert advisory board for structural engineering guidelines at the time of preparation. The decision on the interpretation of the building regulations in a specific building procedure lies with the responsible building authority.

Point: 2 Supporting graphics2025-03-13T11:04:23+01:00
Point: 2.1 Supporting graphics2025-03-13T11:01:25+01:00
Point: 2.2 Supporting graphics2025-03-13T11:00:36+01:00
Point: 4.1 Supporting graphics2025-03-13T10:56:54+01:00
Point: 4.2 Supporting graphics2025-03-13T10:55:45+01:00
Point: Table 1 Point 2.1, 2.2 and 2.3 Supporting graphics2025-03-13T10:54:13+01:00
Point: Table 1 Line 2 Supporting graphic2025-03-13T10:50:56+01:00
Point: Table 1 Line 2 Supporting graphic2025-03-13T10:45:55+01:00
Point: 2 Supporting graphics2025-03-12T22:14:57+01:00
Point: 4 How should the calculation of the overall energy efficiency factor fGEE and its comparison with requirements be carried out if there are multiple systems (different heat suppliers) for one calculation zone (e.g. single-family house with 70 % direct electricity heating and 30 % individual wood stove)? 2025-03-12T12:22:54+01:00

Although the 2015 edition of the guidelines for OIB Guideline 6 specifies how the distribution, distribution, storage and supply losses in multiple systems are to be divided, there are no further regulations on how to calculate the overall energy efficiency factor fGEE for such mixed systems and how to deal with requirements when comparing them.

These regulations are missing for good reason, as the situation is complex. For the calculation of the energy performance factor fGEE, for example, it is in no way permissible to add up the final energy for both the real equipment (EEB) and the reference equipment (EEB26) in a weighted manner and to set them in relation to each other. This is because this approach combines different energy systems in terms of final energy, which are in no way comparable in terms of energy use. This is precisely why the energy performance factor was introduced, because the different energy systems are not comparable at the final energy level.

Note: However, the calculation of the final energy demand for the specification in the energy performance certificate and the specification of the maximum permissible final energy demand as the required value by adding up the respective proportions is correct.

In the above example, the final energy of the direct electric heating or the air heat pump as the corresponding reference equipment cannot be combined or weighted with the final energy of a wood-burning stove or the corresponding reference equipment of a pellet boiler for the calculation of the overall energy efficiency factor fGEE due to the absolutely different energy inputs.

 

The following procedure should therefore be followed with regard to fGEE:

If more than 80 % of the gross floor area is supplied by one heating system, the different supply systems can be combined according to the zoning criteria and proof of the fGEE for this heating system must be provided.

In other cases, the fGEE of the individual zones must be calculated with the respective supply systems and compared with the requirement value of the respective zone.

Alternatively, the calculation can be carried out for the entire building (of a building category) with the different supply systems, assuming that they each supply the entire building. These fGEE values must then be weighted over the gross floor area and combined to form an fGEE and compared with the requirement. Rooms with two supply systems at the same time (e.g. living room with central heat supply with underfloor heating AND individual wood-burning stove) are to be divided into equal parts of the floor area for the weighting of the fGEE.

 

Note on individual stoves: In cases where the majority of the building is to be heated by a single stove, it must be checked whether heat distribution to all parts of the building is guaranteed.

Point: 4.2.2 Why does the footnote in the tables on the requirements for non-residential buildings in point 4.2.2 refer to the residential building usage profile and should the introductory sentence of the second table in this section not read “If the energy performance factor is used to demonstrate compliance with the requirements for non-residential buildings, the following maximum values apply”? 2025-03-12T12:22:06+01:00

Yes, of course the second introductory sentence should announce the requirements for non-residential buildings by analogy with the first introductory sentence. The reference to the residential building usage profile when verifying the requirements is correct. This is due to the fact that some usage profiles have such a high air change rate in their usage profile that the ventilation losses alone would rule out a positive undercutting of the requirement values. At the same time, this type of requirement setting offers the advantage that requirements are always met in the event of subsequent changes of use. This corresponds to the earlier concept of the HWB* (residential building equivalent, area-related heating requirement).

Point: 4.3 Is it also possible to meet the required minimum proportion of energy from renewable sources through “increased efficiency” alone (cf. lit. b, fourth indent)? 2025-03-12T12:21:38+01:00

Yes, the required minimum proportion of energy from renewable sources can also be demonstrated by “increasing efficiency” alone (e.g. by exceeding the requirements for the building envelope or by a corresponding improvement in the heating technology energy requirement). The phrase “any combination” therefore also includes the application of only one of the measures listed.

Point: 4.3 What does net final energy on site or in the vicinity or final energy demand for hot water mean in point 4.3 of OIB Guideline 6, 2015 edition? 2025-03-12T12:21:01+01:00

Net final energy at the location or in the vicinity or final energy demand for hot water in point 4.3 of OIB Guideline 6 means the amount of energy that results from a monovalent hot water heat demand calculation without generating yields.

This means that any auxiliary energy shares for the solar thermal system must also be generated with regard to the final energy, i.e. the system must be dimensioned larger by this share than in a calculation at the useful energy level or hot water heat demand level.

Point: 4.4.1 Which U-value requirements apply to inclined transparent components, windows, French windows, glazed doors and skylights? 2025-03-12T12:20:41+01:00

Up to an inclination of 60°, the requirements for inclined transparent components, windows, French windows, glazed doors and skylights apply; above an inclination of 60°, the requirements for windows, French windows and glazed doors apply.

Point: 8 Have the conversion factors fPE. ern. for heating oil and fPE. n.ern. natural gas have been changed? 2025-03-12T12:20:14+01:00

No, these are editorial errors. The conversion factor fPE.ern. is 0.00 and the fPE.n.ern. for natural gas is 1.17 – as in the 2011 edition.

Point: 9 Which system should be used to determine reference equipment if the equipment used is not listed under point 9 Reference equipment, and which system should be used to determine the energy performance factor for final or delivered energy? 2025-03-12T12:19:29+01:00

In principle, all the reference equipment defined in points 9.2.1 to 9.2.10 of OIB Guideline 6 follow the idea that combined systems exist.

 

If there is a separate heat supply in which the heat for space heating is provided by a direct electricity heating system and the heat for hot water is provided by a heat pump, an air/water heat pump in accordance with point 9.2.12 is to be used as the reference equipment for the direct electricity heating system and a heat pump with the same heat source as the real equipment for the hot water heat pump.

 

To determine the requirements for the final energy demand and the overall energy efficiency factor, only the supply energy demand for the reference equipment “air/water heat pump according to point 9.2.12” is to be taken into account.

 

In all other cases, especially in those cases in which heat is provided separately for space heating and hot water or with different heat suppliers, only values for the final energy demand are to be used to determine the requirements for the final energy demand and the overall energy efficiency factor.

 

If, as in point 9.2.11, the heat for hot water is provided by direct electric heating, direct electric heating must also be used as the reference equipment, irrespective of how the heat is provided for space heating.

 

Point: 9.2 What reference equipment should be provided for an exhaust air heat pump? 2025-03-12T12:19:09+01:00

An air/water heat pump is to be used as reference equipment. A separate reference equipment will be developed in the future.

Point: 12.3 Can proof of summer thermal insulation be provided by means of sufficient storage masses using the simplified procedure of ÖNORM B 8110-3:2012 if not all windows can be kept open at night? 2025-03-12T12:18:22+01:00

Yes, this is possible for compliance with the requirements of OIB Guideline 6, as it is not a matter of the normative proof of the avoidance of summer overheating, but of the proof of sufficient storage masses.

Point: Annex (model energy performance certificate) Where can the recipient of an energy performance certificate obtain more detailed information on how to obtain the recommendations for cost-optimal or cost-effective improvement of energy performance required under Article 11 of the EPBD? 2025-03-12T12:18:03+01:00

Address of the energy performance certificate issuer.

Point: 2.2.5 How is the regulation in point 2.2.5 of OIB Guideline 5 to be interpreted for non-closable ventilation openings? 2025-03-12T12:16:27+01:00

In the case of non-closable ventilation openings, a protection target-oriented design is required. Based on the R’res,w, this results in a sound insulation level that must be achieved even if ventilation units are present.

Relief is only available for closable ventilation openings in the open position, as the sound insulation level can be achieved by closing the openings. If the openings cannot be closed, the requirements for the required R’res,w apply.

Point: 2.10.3 To which reference line does the maximum inclination of helical ramps refer? 2025-03-12T12:15:51+01:00

In accordance with RVS 03.07.32, the ramp gradient refers to the center of the roadway.

Point: 2.10.4, Table 2 2025-03-12T12:15:33+01:00

This FAQ has been deleted, as point 0 (preliminary remarks) of OIB Guideline 4 has created the possibility for an equivalent deviation:

“The requirements of this OIB Guideline may be deviated from in accordance with the respective provincial regulations if the building applicant can prove that the same level of protection is achieved as with the application of the Guideline.”

The examination of the equivalent deviation is carried out by the competent building authority.

Point: 3.1.1 Are only the µ values relevant for determining the slip resistance of floor coverings, and is the study “Measurements of the coefficient of sliding friction to assess the µ value of walkable surfaces” cited in the Explanatory Notes to OIB Guideline 4, March 2015 edition, on point 3.1.1 binding? 2025-03-12T12:15:13+01:00

No, R-values or other characteristic values can also be used.

Point: 3.1.1 Are only the µ values relevant for determining the slip resistance of floor coverings, and is the study “Measurements of the coefficient of sliding friction to assess the µ value of walkable surfaces” cited in the Explanatory Notes to OIB Guideline 4, March 2015 edition, on point 3.1.1 binding? 2025-03-12T12:14:56+01:00

No, R-values or other characteristic values can also be used.

Point: 3.2.5 Do handrails also have to be installed in the landing area of stairs in accordance with point 3.2.5? 2025-03-12T12:14:38+01:00

No, according to point 3.2.5, handrails on stairs only have to be installed in the area of the steps and therefore only at the flight of stairs, but not in the area of the landings. Only in buildings or parts of buildings that are to be designed barrier-free are the handrails to be extended 30 cm beyond the edge of the steps.

Point: 2.7.1 Does the width of the usable clearance of doors in WC partition systems have to be at least 80 cm? 2025-03-12T12:13:57+01:00

No, as these are furnishings, it is possible to deviate from point 2.7.1 of OIB Guideline 4, March 2015 edition. The width must not be less than 60 cm. This corresponds to § 33 (6) of the Workplace Ordinance (AStV).

Item: 2.9.1 Why do doors in buildings or parts of buildings that are to be designed to be barrier-free have to have access areas on both sides of the door that protrude at least 50 cm beyond the headroom on the side of the lever handle or door handle? 2025-03-12T12:12:33+01:00

Due to various disabilities, people in wheelchairs or with rollators have limited or no mobility in their upper body and cannot bend forwards, for example, or only have one hand trained for gripping. For this reason, they must position the wheelchair or rollator parallel to the side of the door leaf in order to operate the door, which is why the approach area must be guaranteed on both sides of the door.

Point: 2.9.2 Can the required ease of use of doors (point 2.9.2 in conjunction with point 7.4.2 of OIB Guideline 4, March 2015 edition) also be ensured retrospectively for apartment entrance doors with self-closing function? 2025-03-12T12:12:10+01:00

Yes, as the apartment entrance door is assigned to the apartment, the barrier-free adaptability within the meaning of point 2.9.2 in conjunction with point 7.4.2 of OIB Guideline 4, March 2015 edition, also applies to the apartment entrance door. However, as the adaptability must be achieved without considerable effort, the corresponding preparations (such as empty pipework) must be carried out in advance for subsequent installation measures of free swing door closers, power-assisted drives, fully automatic drives with fire control, etc.

Point: 2.9.2 What is meant by “easy to use” according to point 2.9.2? 2025-03-12T12:11:52+01:00

A door without a door closer is easy to operate in standard operation if it does not exceed the operating forces and torques of class 3 in accordance with ÖNORM EN 12217 (e.g. 25 N for opening the door leaf on swing doors and sliding doors).

A door with a door closer (e.g. fire and smoke protection doors) is easy to operate in standard operation if it does not exceed the opening torque of door closer size 3 in accordance with ÖNORM EN 1154.A door with a door closer (e.g. fire and smoke protection doors) is easy to operate in normal operation if it does not exceed the opening torque of door closer size 3 in accordance with ÖNORM EN 1154.

Higher operating forces and opening torques are permitted in the event of a fire.

Point: 10.1.2 Is the limit value of 45 dB for the relevant external noise level, above which natural ventilation is no longer possible, stated in the Explanatory Notes to OIB Guideline 3 also intended for short-term ventilation processes? 2025-03-12T12:10:29+01:00

No, short-term ventilation processes (shock ventilation) are not affected.

Point: 5.3.3 May cleaning openings of flue gas collectors be located in apartments that are assigned to this flue gas collector? 2025-03-12T12:10:01+01:00

Yes, OIB Guideline 3 stipulates as a requirement for access to cleaning openings that access to cleaning openings must not be via other residential or commercial units. If the residential or commercial unit in which the cleaning opening of the flue gas collector is located is connected to the flue gas system, then this residential or commercial unit is not an “other” dwelling.

Point: 3.1.1 Is the area of the stairwells to be included when determining the net floor area of the fire compartments? 2025-03-12T11:55:47+01:00

No.

Point: 3.1.1 In accordance with point 3.1.1. of OIB Guideline 2, no requirements are set with regard to the maximum net floor area of fire compartments in residential buildings. Does this also apply to other types of use for residential buildings that are only predominantly used for residential purposes (see definition)? 2025-03-12T11:55:17+01:00

No, for buildings with mixed use, the provisions of the OIB Guidelines for the respective use must be applied for the individual areas of use (see Explanatory Notes on OIB Guideline 2, under point 0 “Preliminary remarks”).

Point: 3.1.7 Graphics2025-03-12T11:55:12+01:00
Point: 3.1.8 Graphics2025-03-12T11:54:49+01:00
Point: 3.2.1 Do the provisions of point 3.2.1, second sentence, of OIB Guideline 2 also cover rooms used for hospitality purposes? 2025-03-12T11:54:19+01:00

As rooms used for catering purposes are not explicitly mentioned, they must be assigned to a type of use.

In the case of point 3.2.1, second sentence, rooms used for catering purposes can be included in this up to the maximum fire compartment area, as they are comparable to retail premises in terms of fire protection.

Point: 3.1.9 Graphics2025-03-12T11:53:50+01:00
Point: 3.4 Do the requirements of the second paragraph of point 5.1 of TRVB 110 B 15 with regard to individual lines correspond to the target-oriented requirements of point 3.4 of OIB Guideline 2? 2025-03-11T11:56:45+01:00

Yes, individual cables, with the exception of empty conduits, with a maximum diameter of 25 mm may be routed through components with fire protection requirements at a distance of at least 1 m from each other, even without tested or classified penetration sealing measures, if the opening is designed to fit the cable diameter precisely.

Point: 4.1Graphics2025-03-10T11:58:26+01:00
Point: 4.2 Is fire transmission to buildings on neighboring properties not to be expected in the case of “subordinate single-story buildings” (point 4.2 lit. b) only if the buildings on the neighboring property are located at least 4.00 m away, as mentioned in the Explanatory Notes? 2025-03-10T11:57:09+01:00

No, if the buildings on the neighboring property are “subordinate single-story structures”, buildings of GK 1 or terraced houses of GK 2, a distance of 2.00 m between these buildings is also sufficient.

Point: 7.1.4 Is the area of the salvage room to be taken into account when determining the net floor area of the fire compartment? 2025-03-10T11:00:08+01:00

Yes, the area of the salvage room is included in the net floor area of the fire compartment.

Point: Table 1a, line 4.1 Do skylight domes, continuous rooflights and the like require BROOF (t1)? 2025-03-09T12:10:39+01:00

No requirement for BROOF (t1) is necessary for skylight domes, continuous rooflights and the like, which in total do not exceed 15 % of the associated roof area.

Item: Table 1b line 3, Supporting graphics 2025-03-09T12:05:07+01:00
Point: Table 1b line 1, 2.4 and 3, Supporting graphic2025-03-09T12:04:37+01:00
Point: Table 1b line 1 and 2, Supporting graphic2025-03-09T12:03:49+01:00
Point: Table 1b line 1 and 3 in connection with footnote 2 Supporting graphic2025-03-09T12:02:07+01:00
Point: Table 1b, lines 4.1 and 4.4 Do the requirements of lines 4.1 and 4.4 of Table 1b of OIB Guideline 2 apply to the entire ceiling? 2025-03-09T11:59:06+01:00

No, the requirements in lines 4.1 and 4.4 of Table 1b of OIB Guideline 2 only refer to the load-bearing capacity (R) and therefore only to the load-bearing components (primary load-bearing structure).

Point: Table 2b, line 8 What does “Internal alarm” mean in Table 2b, line 8 for the fire alarm system? 2025-03-08T12:00:59+01:00

“Internal alerting” means that sirens are only to be installed in the monitored areas (stairwells including generally accessible areas such as corridors and cellars), but not in apartments and other usage units.

 

Supporting graphic point: 0 2024-04-29T13:05:35+02:00
Supporting graphics point: 4.1 2024-04-29T11:15:11+02:00